Guides / Fuse size calculator: what size fuse for each van circuit
Fuse size calculator: what size fuse for each van circuit
The short answer
Size each fuse to protect its wire: never above the cable's current rating, and for a single device no higher than the device's rating, unless its manual names a fuse, which comes first. Put it in the positive cable at the source, within 7 in of the battery. On lithium, the main fuse needs an interrupt rating that covers the bank's short circuit current, usually a Class T.
Last updated 24 November 2026
Key takeaways
- A fuse protects the wire: Victron's rule is never rate it above the cable, and with one device, no higher than the device's rating either.
- Take the fuse from the device's manual first: Victron's MPPT 100/30 wants 35 to 40 A, a REDARC BCDC1250D a 60 A input fuse, a Samlex PST-2000-12 inverter 250 A.
- Every positive wire leaving the battery gets its own fuse, placed at the source; Samlex and the Coast Guard boat rule both say within 7 in.
- On lithium, at least one fuse must interrupt the bank's full short circuit current; Class T fuses in Victron's table are rated 20,000 A or more.
- Use DC rated fuses for your system voltage: most blade, MIDI, MEGA and ANL fuses in Victron's table are rated 32 V DC.
Fuses sit on top of wire sizing, so pick the cable first with the wire size calculator; the whole layout is in how to wire a camper van.
What does a fuse protect?
The wire, first. Victron says a fuse protects wires from currents high enough to overheat them or start a fire, and protects equipment too. When current above its rating flows long enough, the fuse opens and the circuit stops.1
That is why the cable, not the appliance, sets the ceiling. Victron's current rating rule: with one consumer on a circuit, the fuse matches the consumer's rating or the cable's rating, whichever is lower; with several consumers, it matches the cabling.1 A fuse also needs a voltage rating at or above the system's maximum and must be rated for DC; Victron notes most DC fuses suit 12 and 24 V but not necessarily 48 V and higher.1
A note on the Coast Guard rule. 33 CFR 183.455, written for boats with gasoline engines, lets a fuse go up to 150% of the conductor's Table 5 amperage on circuits under 50 V, and up to the Table 5 value at 50 V or more.23 Vans are not covered by it. We use Victron's stricter rule throughout, as our other electrical guides do, so the table below never exceeds the cable's rating.
How do you pick a fuse for each wire size?
Find the cable's ampacity for its insulation rating, and keep the fuse at or below it. For 105 °C wire, Table 5 gives 45 A for 12 AWG, 80 A for 8 AWG, 160 A for 4 AWG and 330 A for 2/0. Then check the device manual.41
This is the fuse sizing table to copy. Read the jacket of your cable for its temperature rating and use that column. If no standard fuse matches the number exactly, choose the next one down. The figures are for a single conductor outside an engine space; Table 5 derates bundles and engine spaces, so go lower there.4
| Wire | 60 °C insulation | 75 °C | 90 °C | 105 °C |
|---|---|---|---|---|
| 16 AWG | 15 A | 15 A | 25 A | 25 A |
| 14 AWG | 20 A | 20 A | 30 A | 35 A |
| 12 AWG | 25 A | 25 A | 40 A | 45 A |
| 10 AWG | 40 A | 40 A | 55 A | 60 A |
| 8 AWG | 55 A | 65 A | 70 A | 80 A |
| 6 AWG | 80 A | 95 A | 100 A | 120 A |
| 4 AWG | 105 A | 125 A | 135 A | 160 A |
| 2 AWG | 140 A | 170 A | 180 A | 210 A |
| 1 AWG | 165 A | 195 A | 210 A | 245 A |
| 1/0 AWG | 195 A | 230 A | 245 A | 285 A |
| 2/0 AWG | 225 A | 265 A | 285 A | 330 A |
| 3/0 AWG | 260 A | 310 A | 330 A | 385 A |
| 4/0 AWG | 300 A | 360 A | 385 A | 445 A |
Ampacity from 33 CFR 183.425 Table 5, stranded copper outside engine spaces; the fuse ceiling is Victron's rule. 18 AWG is left out because Table 5's rules start single conductors at 16 AWG.41
Fuse size calculator (12 V and 24 V DC)
Pick the wire you are using, then the device. If the device's manual names a fuse, enter it to check it against the wire.
Largest fuse: 20 A
- Cable: 10 AWG at 105 °C is rated 60 A (33 CFR 183.425 Table 5).
- One device rated 20 A: Victron's rule takes the lower of the device and the cable, 20 A.
- If no standard fuse has exactly this rating, pick the next one down. Use a DC rated fuse for your system voltage.
Single conductor outside an engine space; derate for bundles and engine spaces. On lithium, the main fuse also needs an interrupt rating that covers the bank's short circuit current. This does not size the wire: use the wire size calculator for voltage drop first.
Source: 33 CFR 183.425 Table 5 and Victron Wiring Unlimited section 4.6, read 24 November 2026; chart ours.41
Worked example, using the wire calculator's maths: a 20 A load 10 ft from the fuse block at 12 V and 3% drop needs 8 AWG, rated 80 A at 105 °C. The cable could take an 80 A fuse, but with one device on the circuit Victron says match the lower figure, so the fuse is sized to the device, unless its manual names another.41
What fuse does each part's manual ask for?
Use it whenever the manual gives one. Victron's MPPT 100/30 asks for 35 to 40 A on the battery side, its Orion XS 50 A charger 60 to 70 A, REDARC's BCDC1250D a 60 A input fuse, and Samlex's PST-2000-12 inverter a 250 A Class T or equivalent.6895
| Part | Fuse | Where |
|---|---|---|
| Victron SmartSolar MPPT 100/30 | 35 to 40 A6 | Battery side of the controller |
| Victron SmartSolar MPPT 100/50 | 55 to 70 A6 | Battery side of the controller |
| Victron SmartSolar MPPT 150/35 | 40 to 45 A7 | Battery side of the controller |
| Victron SmartSolar MPPT 150/45 | 50 to 63 A7 | Battery side of the controller |
| Victron Orion XS 12/12-50A DC-DC | 60 to 70 A8 | In the cable run, per the manual's table |
| REDARC BCDC1225D DC-DC | 40 A input; FK40 fuse kit recommended on the output9 | At each battery, as close to the terminal as possible |
| REDARC BCDC1240D and BCDC1250D | 60 A input; FK60 fuse kit recommended on the output9 | At each battery, as close to the terminal as possible |
| Samlex PST-2000-12 inverter | 250 A, Class T or equivalent5 | Within 7 in of the battery positive |
| Victron Inverter VE.Direct 120V 12/1200 | Internal 200 A MIDI; add one if the cable is over 1.5 m10 | Added fuse close to the battery |
| Victron Inverter Smart 12/2000 (230 V) | 300 A, external (none inside)11 | Battery cable |
| Victron Inverter Smart 12/3000 (230 V) | 400 A, external (none inside)11 | Battery cable |
Then check the manual's fuse against your cable. If the cable you plan is rated below the manual's fuse, the cable is too thin: go up a size rather than down a fuse that the device may blow in normal use. Battle Born recommends an ANL fuse between its batteries and the inverter or loads, and says all cables must be able to carry the high currents the battery can deliver.12 The Victron Inverter Smart rows are its 230 V models, listed because the manual gives the DC fuse; the DC current depends on watts and battery voltage, not on the AC voltage.11
Which fuse types are used in a van?
Blade fuses in the fuse block for small loads, MIDI or MEGA for chargers and busbar feeds, ANL or MRBF for large feeds, and a Class T as the lithium main fuse. Most blade, MIDI, MEGA and ANL fuses in Victron's table are rated 32 V DC.1
| Type | Current range | Max DC voltage | Speed | Typical van use (ours) |
|---|---|---|---|---|
| Blade (automotive) | Up to 120 A | 32 V DC | Slow | Fuse block circuits: lights, fan, pump, USB |
| MIDI | 23 to 200 A | 32 V DC | Slow | Chargers and mid-size feeds |
| MRBF (terminal fuse) | 30 to 300 A | 58 V DC | Marine rated | Bolts straight onto a battery post or busbar |
| MEGA | 40 to 500 A | 32 V DC | Slow | Busbar and inverter feeds |
| ANL | 35 to 750 A | 32 V DC | Fast | Inverter and main feeds |
| Class T | Not given in the table | 125 to 300 V | Fast, very high interrupt rating | Main fuse on a lithium bank |
Ranges, voltages and speeds from Victron Wiring Unlimited section 4.6; the last column is our summary of where each is used.1
Speed matters for inverters and motors. Victron says slow blow fuses are common in automotive and marine DC circuits because they ride through short start-up surges from motors and from devices with capacitors, such as inverters.1
Where must fuses be placed?
In the positive cable, at the power source. Victron fuses every consumer individually after a main battery fuse; Samlex puts its inverter fuse within 7 in of the battery; a DC-DC charger run needs a fuse at each battery, since both can feed a short.159
Our diagram, simplified: negatives return to a negative busbar. Rules from Victron (each consumer fused in the positive cable, a main fuse, a fuse between array and solar charger), Samlex (7 in) and REDARC (both batteries).159
The 7 in figure appears in two places we opened. Samlex asks for its Class T fuse within 7 in, or 178 mm, of the battery positive.5 The Coast Guard boat rule puts the fuse at the source of power, or within 7 in along the conductor where that is impractical, or within 40 in if the conductor is inside a sheath or enclosure the whole way.2 Victron adds that systems with several inverters fuse each unit separately with the same fuse type, because one big fuse may not trip for a fault in a single unit.1
One safety step from Samlex's manual: an inverter's input capacitors draw a heavy current the moment the circuit is closed, so fit the external fuse last, once every other connection is made, to keep the spark at the fuse.5
When do you need a Class T fuse?
With lithium batteries, for the main fuse. Victron says at least one fuse in the line must interrupt the bank's maximum short circuit current, a mandatory rule; Samlex asks for Class T or equivalent with at least 10,000 A interrupting capacity for its inverters.15
Source: Victron Wiring Unlimited section 4.6.1 fuse overview, and Samlex PST manual section 8.4.4, read 24 November 2026. Bar length is logarithmic (each step is ten times more); chart ours.15
Victron explains why: a lithium bank can deliver far higher short circuit currents than a comparable lead acid bank, and a fuse whose interrupt rating is lower than the available fault current may fail catastrophically. Victron calls the Class T fuse well suited to lithium, and allows other types if their current, DC voltage and interrupt ratings match the system.1 Samlex says a Class T blows in under 8 ms on a short circuit, and also allows MRBF terminal fuses.5
You need the bank's short circuit current to check this. Battle Born's BB10012 manual lists short circuit protection in the battery management system but gives no short circuit current figure,12 so ask your battery's maker for it. Parallel batteries add their currents, so a bigger bank needs more interrupt rating.
Who sells fuses and fuse blocks?
Verified makers in our directory that publish fuse and cable specs include Victron Energy and Battle Born; complete van wiring kits come from EXPLORIST.life.
The rest are in our parts directory. The cluster: the whole system, wire size, lithium batteries, inverters, solar charge controllers, solar panels and DC-DC chargers. Every build topic is on the DIY hub. Not sure about any of it? Have a qualified electrician check the work before the walls close, and use a licensed electrician for anything on the 120 V side.
Questions people ask
How do I calculate fuse size for a 12V circuit?
Use the fuse the device manual names. If there is none, Victron's rule is the fuse must not exceed the lower of the device's current rating and the cable's rating; with several devices on one cable, match the cable. Then check the fuse is DC rated for your voltage.
Does the fuse protect the wire or the device?
Mainly the wire. Victron's wiring book says a fuse protects wires in a circuit from currents high enough to overheat them or start a fire, and protects equipment too. That is why the fuse can never be rated above the cable it feeds.
How close to the battery should the main fuse be?
As close as practical. Samlex asks for its inverter fuse within 7 in of the battery positive. The Coast Guard boat rule, 33 CFR 183.455, puts fuses at the source of power or within 7 in, or within 40 in if the cable is in a sheath.
Do I need a Class T fuse for a lithium battery?
You need at least one fuse whose interrupt rating covers the bank's maximum short circuit current, which Victron calls mandatory for lithium. Class T fuses are rated 20 kA and up in Victron's table. Samlex asks for Class T or equivalent with at least 10,000 A interrupting capacity.
Can I use a circuit breaker instead of a fuse?
Yes, if it is rated for DC at your voltage and the current. Victron notes some DC breakers are not unidirectional, so wire them the right way round. REDARC advises against self-resetting breakers on its chargers because heat can trip them early.
Is a 150% fuse allowed under the Coast Guard rule?
On gasoline-engine boats, 33 CFR 183.455 allows a fuse up to 150% of the Table 5 amperage on circuits under 50 V. Vans are not boats, and this guide follows Victron's stricter rule: never above the cable's rating.
Does an inverter with internal fuses still need an external one?
Yes. Samlex says its internal DC fuses protect the inverter's own parts and will not blow for a short along the battery cables, so the external fuse is mandatory. Victron's 120 V inverters need an added fuse close to the battery when the cable is over 1.5 m.
What size fuse block do I need?
One with a circuit for every 12 V load, since Victron says each consumer gets its own fuse, plus spares, and a feed fuse no larger than the feed cable's rating. Check the block's own maximum per circuit and total current in its spec sheet.
Sources
Fuse rules are from Victron's Wiring Unlimited and the component manuals named in each row; wire ampacity is from 33 CFR 183.425 Table 5, the same table our wire size calculator uses. 33 CFR 183.455 was opened and is reported, but it governs boats, and where it allows more (150%) we follow Victron's stricter rule. ABYC E-11 and Blue Sea Systems' and fuse makers' own data sheets could not be opened, so we do not quote them. All read 24 November 2026.
- Victron Energy, Wiring Unlimited, chapter 4: DC wiring, section 4.6 DC fuses and circuit breakers, and 4.6.1 interrupt rating for lithium systems. Read 24 November 2026
- US Coast Guard, 33 CFR 183.455, Overcurrent protection: General (eCFR, current). Read 24 November 2026. A rule for boats, not vans
- US Coast Guard, 33 CFR 183.401, Purpose and applicability of the electrical subpart (eCFR, current). Read 24 November 2026
- US Coast Guard, 33 CFR 183.425, Conductors: General, Table 5 Allowable Amperage of Conductors (eCFR, current). Read 24 November 2026
- Samlex America, PST-1500 and PST-2000 pure sine wave inverter owner's manual (document 11001, July 2026), sections 1.3.4, 8.4.3 and 8.4.4. Read 24 November 2026
- Victron Energy, SmartSolar MPPT 100/30 and 100/50 manual, Installation. Read 24 November 2026
- Victron Energy, SmartSolar MPPT 150/35 and 150/45 manual, Installation. Read 24 November 2026
- Victron Energy, Orion XS 12/12-50A DC-DC battery charger manual, Installation. Read 24 November 2026
- REDARC, BCDC Dual Input In-Vehicle Battery Charger instruction manual (BCDC1225D, BCDC1240D, BCDC1250D). Read 24 November 2026
- Victron Energy, Inverter VE.Direct 120V manual, Installation (battery connection table). Read 24 November 2026
- Victron Energy, Inverter Smart manual, Installation (battery connection table; 230 V models). Read 24 November 2026
- Battle Born Batteries, BB10012 100Ah 12V LiFePO4 battery manual (document PMI_BB10012, revision 038, 12 August 2026). Read 24 November 2026